Friday, September 11, 2015

Cyber physical attacks to critical infrastructure (Part II: Attack and defense)


Although the number and nature of cyber attacks on control systems that could have effects on the physical environment is very broad, we will only consider those that have been studied by various stakeholders in the industrial Cyber Security.

In particular, recent studies define the following categories depending on the purpose of physical cyber attack:
  • Damage to equipment 
  • Damage to Production 
  • Deterioration of compliance
Let’s see each of them in detail:


Damage to equipment


Such cyber attacks are intended to produce permanent failures and breakdowns industrial equipment interacting with the physical environment. In particular, attacks have been studied on the following elements:

  • Pipes and pipelines: The valve opening and closing quickly, and sometimes coordinated, is capable of causing a physical phenomenon called "water hammer" consisting of an increase in pressure inside the pipe can be higher than the structural strength thereof, causing breakage and subsequent discharge of fluid (liquid or gas) to drive.
  • Tanks: In many cases Tanks are designed to withstand very high internal pressures, but at very low internal pressure (or vacuum), collapse. Sudden changes in the temperature inside a tank can lead to abrupt changes in internal pressure, which could eventually collapse it.
  • Generators: As demonstrated in the Aurora experiment, opening and closing off phase switches from a generator connected to an electrical substation produce kinetic effects that just physically breaking it.
  • Engines: Stuxnet cyber attack in the last phase tended to accelerate the engines of uranium centrifuges for long periods of time causing material fatigue and subsequent failure.
  • Chemical Reactors: The most common chemical reactions typically occur at high temperatures, so a change in the conditions of reaction control may be associated with a significant increase in temperature would cause thermal damage to the reactor structure, reaching its total destruction.


It is also possible to combine two or more of these attacks each other, so that the power loss is associated with a loss of control of some element or its inlet in an unstable operating condition.
Although we have been considering these as attacks, there are historical examples on great industrial accidents caused by abnormal functions in control systems.
The following points will demonstrate how these detection technologies can help on detecting some operational failures that could lead to serious industrial accidents as well.

Damage to Production


The purpose of this type of cyber attacks to the process is altering the financial results of the organization that operates such processes. Among them they have been studied the following:

  • Decrease the amount of final product: By changing certain variables control the process at specific points, you can alter the amount of product obtained. A clear example of this is built on the production of vinyl acetate monomer [7] Black Hat in Las Vegas in August 2015.
  • Decrease in product purity: If the alterations made to the process control variables do change the purity of the final product, you can produce a significant devaluation of the same. A concrete example is the Paracetamol, whose purity can alter the price by several orders of magnitude.
  • Increase in operating and maintenance costs: Cyber ​​attacks can cause alarm processes intentionally to force recalibration of the field elements as often as desired attackers, thereby increasing the costs of the targeted organization. Moreover, repeated attacks on processes with different values ​​is one of the most common practices of hiding them, because that way the suspicions maintenance teams move the organization.

Deterioration of compliance


Legal and regulatory frameworks to be met by organizations, makes certain commitments made by them can have very significant penalties for breach thereof. Among this kind of commitment we can find the following:
  • Safety regulations: Altering a security parameter of the industrial plant may entail a violation of any rules of physical security which in turn is liable to a major fine if inspection.
  • Impact on the environment: discharges into rivers or waste production values of certain compounds above the permissible threshold are punished with significant financial penalties.
  • Contractual breaches: The purity or quantity alteration of the product can make certain clauses of the contracts do not meet preventing accorded billing and causing significant economic losses to the organization.
All these cyber attacks studied in the past year, have a number of common characteristics:

  • Semantic attacks: They are necessary depth knowledge of the environment, the process and the variables to be altered to produce the desired effects.
  • Targeted to the control network: Using "legitimate” users and systems, over unauthenticated control protocols and "valid" commands, and executed with appropriate permissions.
  • Conducted by multidisciplinary teams: Composed by an IT team (Network and Systems), an OT team (SCADA) and process engineers (of the attacked sector)
  • In view of the nature of cyber-physical and processes attacks, and the above on the technical characteristics of the control networks, critical infrastructure protection presents a number of problems that can only be addressed using the solutions that describe the next point.

It might seem that this type of attack is too complicated or exceptional to take into account in our risk analysis, but do not forget that:

  1. They are targeted attacks intended to cause physical damage and could be executed or sponsored by state organizations.
  2. Already they materialized before and were not mere theoretical laboratory studies.
  3. In both cases the cyber attack had an external source to the facilities attacked even when isolated from the Internet is assumed. (The average number of connections found in control networks assessment is 11)
  4. The success of these attacks could endanger human lives.
  5. The PIC 8/2011 of Critical Infrastructure Protection Act explicitly mentions the need to consider in the risk assessment of this type of infrastructure events of very high impact, such as the case of these attacks.

Another common thinking when suppressing these cyber-physical attacks from risk analysis could be considering them covered by safety plans. As showed in the Mogford report after the Texas City refinery accident, there was a lack of preventative maintenance on safety critical systems. So once again, we can not relay on initial conditions to establish the actual security state of infrastructure, we need to assess it on a periodic basis.


Critical Infrastructure Protection


Cyber security is founded on three pillars: people, procedures and technologies. In this case it cannot be otherwise, so these sections formulate a series of recommendations to protect such infrastructure from cyber-physical attacks seen before.

People


As we saw earlier in this note such cyber attacks can only materialize through joint action of experts in different fields (IT Technology, OT technology and Industrial process to attack). It is necessary for critical infrastructure have multidisciplinary teams in their Cyber Security organizations working in a coordinated way in order to protect them.
This is one of the most common problems encountered in implementing the CIP law because the existing inertia in many organizations  the world of control and security have always been in different functional areas and with different officials and budgets.
The awareness of senior management of the infrastructure operator is required to make critical changes needed in the functional organizations to ensure a unique multidisciplinary team responsible for this Cyber Security.

Procedures


It is a priority to establish changes in the procurement procedures of the critical infrastructure operators requiring the inclusion of Cyber security requirements for solutions in automation and control, just as there are for safety on plants. Deploying controls and countermeasures in the control networks without this approach in design will be much more difficult and expensive  
Given the semantic nature of these attacks is necessary expand risk analysis for contemplating processes attacks. As seen above this is only possible with the participation of process control engineers in this activity where Cyber security and safety come to converge. (Hazard / Risk Analysis).

Technologies


For everything mentioned above, the security measures to be taken in such environments must take into account the importance of availability in such control networks. Any measure to be implemented should be as safe as possible in terms of the impact on the process to protect. According to the Department of Industrial CERT Homeland Security, the impact of the various protection technologies to consider when deploying in such networks is as follows:


  
As can be seen, intrusion detection systems are the technology with less impact on industrial control networks.


Within this technology, and considering the significant limitations that exist for installing third party software on the control systems (SCADA Servers, engineering work stations and operating positions or HMI) is indicated selecting NIDS technology (network Intrusion Detection System) since modification of the existing network architecture or reconfiguring any of the systems won’t be necessary.

Thursday, September 10, 2015

Cyber physical attacks to critical infrastructure (Part III: Detection technologies)


Network intrusion detection System (NIDS)


According to the taxonomy of intrusion detection systems defined by Debar and its working group, the most suitable  System is shown in the following figure:




The detection method should not be based on signatures since it should be frequently updated and it does not offer protection against 0-day vulnerabilities, making detection behavior as the most appropriate choice.
The behavior detection should be passive to be as non-intrusive as possible in the network and not interfere with the commands and actions that are exchanged over the network.
Given the importance of the transitions  have been in the control of industrial processes, the NIDS should consider this type of paradigm, and finally should be monitored continuously since these networks are operating in 24x7x365 basis.

Regarding detection technology for behavioral anomalies, there are several alternatives: inspection message headers (headers) detection, inspection message payload (Payload) detection or a combination of both. In the present note we will use the last option as it is the only one capable of detecting this type of semantic attacks and is used by the deep protocol behavior inspection technology we propose as network intrusion detection in critical infrastructure.

 

NIDS based on deep protocol behavior inspection


Once selected detection technology we will explain how to implement it in such environments. Since its operation is based on detecting events that differ from the normal behavior (anomalies), we must first build the pattern (behavioral blueprint).

The construction of this pattern can be performed on a specific-based manner (introducing the topological and operational information network) or unattended using learning-based technology. The first option is rarely useful as the knowledge of low-level details in the implementation of control networks organizations own is in many cases dating back to the FAT (Factory Acceptance Test) or the SAT (Site Acceptance Test), so usually very old information being outdated and not maintained systematically through change management procedures in line with best practices.

Selecting unattended construction method by learning, we must remember that it is very important that this normal behavior pattern is built in an environment as similar as possible to the production environment on which detecting anomalous behavior is performed.

The scheme of operation of this type of intrusion detection sensors is as follows:


Although learning is automatic it must always be adjusted by control engineers who are familiar with the process to eliminate any undesired operation generated by unscheduled interventions once verified by the control personnel. Additionally, in the phase detection such events should be able to be included in the pattern of behavior (Blueprint)  to avoid unwanted alerts (false positives).

The behavioral blueprint obtained after the learning and customization phase includes the following elements:

Control Network Communication profile

At this time the NIDS knows every possible tuple in the control network (traffic matrix):


Src IP,Src   Port -> Dest. IP,Dest Port



From this moment, we can be alerted by:

• New devices on the network
• Devices trying to connect to our network that are not in our Model
• Devices sending information out of our network to devices out of the model.

Protocols, messages and values matrix

In order to detect advanced operation issues or attack to processes we need to use the technology of deep protocol behavior inspection (DPBI), since with this we will know:

·      The control protocols operating in the network
·      Messages that are used within each protocol
·      The distribution of values within each message field of actual network control protocols.

All this information must be organized in a logical manner in order to obtain the pattern of behavior which subsequently compares all messages obtained from the network. The DPBI NIDS is responsible for generating this model during the learning phase using its advanced technology on behavior modelling.

From this point we can start the detection phase and be alerted of any communication diverge from the newly built behavioral blueprint.

Operational Correlation


Despite the power detection technology DPBI control environments, we need to be able to generate alerts to detect cyber attacks on physical process (operations that are within the behavior pattern and executed from the control network stations also found in the pattern.).

A clear example of this would be a kind Aurora attack and run from a SCADA server to transmit orders for opening and closing of switches out of phase to a remote unit (RTU) in a substation, using the IEC 104 protocol.
To detect this cyber attack, we should be able to store all IEC 104 opening and closing aimed at RTU we found in the control network and estimate the time difference on the immediately preceding command sent to the RTU messages.
To do this the network intrusion detector DPBI also be able to provide the functionality described above. (Operational correlation).

In the case of the NIDS DPBI solution for SCADA SCAB (Security Awareness Control Box for SCADA), this correlation is implemented by deploying additional logic (script type program) that makes this correlation.

An example of a function of this script is as follows:

function new_connection_data(conn, data, is_upstream)
    local record = find_flow(conn)
    if record ~= nil then
        record.up_bytes = conn:upstream_num_bytes()
        record.down_bytes = conn:downstream_num_bytes()
        record.up_pkts = conn:upstream_num_pkts()
        record.down_pkts = conn:downstream_num_pkts()
        record.payload_up_bytes = conn:upstream_num_payload_bytes()
        record.payload_down_bytes = conn:downstream_num_payload_bytes()
    end     
end

Future trends: S-IDS


The combination of detection technology based on control protocol behavioral anomalies, together with the operational correlation allows us to detect cyber-physical attacks on critical infrastructure processes, yet are somewhat craft in regard to the implementation operational and temporal correlations.

To solve this problem it is being investigated in new detection technologies that includes this information in the behavioral pattern automatically.
One of this technology is called Sequence-aware Intrusion Detection System and raises a number of novel approaches in generating a behavior pattern, such as control of the order in which messages are sent and received to the Control elements from the servers, the time between state transitions and sending messages and standard deviation of the time.

The block architecture of a system of this type would be:


In the learning phase information from sources model input (control network protocols messages, log file entries and values of the commands of the process) would be collected and would feed the sequencer to maintain timing trace, before passing to process model generator.

As in the case of NIDS DPBI based, once the learning phase is finished would enter in detection mode. First experimental results for SCADA Waters sector have been achieved and work is in progress to decrease false positive rate (FPR) and noise reduction for the detection phase.

This is just one of today research paths on intrusion detection for industrial control system, but still is under development and validation.

Wednesday, September 9, 2015

Cyber physical attacks to critical infrastructure (Part IV: Detecting Attacks)

Detection of cyber-physical attacks


All cyber-physical attacks exposed earlier in this technical note can be detected using a combination of technologies in network intrusion detection as deep protocol behavior inspection (DPBI) and operational correlation.

  •       Aurora Attack type: After creating the DPBI pattern of normal behavior for the control network, a script that would monitor the sequence of write commands received by the RTUs in an arbitrary period of time (seconds or milliseconds) would be deployed. In the event that an order of writing CLOSE was sent to a given RTU with a previous OPEN value received, at a lower time than the allowed time interval (0.2s), we would fire an alert.


  • Water hammer / discharges Attack Type: Assuming a scenario of progressive control as in Figure 2, would only be possible to reach the completely closed (or open) state for the valve from a previous state with V = 30.



Any value sent in a write command to the PLC control valves would be compared to the last write value sent. If the difference between the value of writing command and the immediately preceding received exceeded the maximum increase in programmed control (∆V = 10), an alert would skyrocket.
Additionally, all values in a command not included in the behavioral blueprint would trigger an alert. (Eg V> 40)

Remarkably, the importance of the anomaly differs depending on the detected transition and a criticality hierarchy may be established. In the example of Figure 2, the abnormal transition E3 -> E5 trigger an alert warning, while the transition anomaly E1 -> E5 trigger a critical alert.

·      Alteration of the amount of production (vinyl acetate monomer): Any value received in the write message on the PLC that controls the temperature of the reactor outside the distribution of values of the behavior blueprint would trigger an alert.

·      Attack by temperature to chemical reactors: As in the case of water hammer, any write command sent to the PLC progressive temperature control would be compared with the immediately preceding. If the difference between the value of writing and the immediately preceding received exceed the maximum temperature defined threshold, an alert would be sent


·      Fake maintenance: Send commands to the control elements in order to conceal attacks on process never would have formed part of the original behavior pattern built for the network, so any transmission of those would trigger an immediate alert.

We can summarize this in the following table:



It is important to note that the semantics needed to detect these attacks through additional programming logic comes from the deep knowledge of the processes controls and possible weaknesses of them. Based solely on deep protocol inspection (DPI) systems could not detect such attacks and it is necessary to use both DPBI and Operational correlation to detect them all.

There is another very powerful implementation of the operational correlation in detecting how allowed control operations (nodes, protocols and distribution of values) are executed on specific time frames. (A firmware update of a PLC or RTU can be normal within one business day and exceptional if done on weekends or at night).


Conclusions


The new attacks on the cyber-physical systems of industrial processes running on critical infrastructure, require the adoption of new strategies capable of detecting without interfering with normal operation.

The change in the functional structures (common Managers and multidisciplinary teams) and the procedures at critical infrastructure operators (Risk Analysis and procurement requirements), it is imperative to address this kind of physical attacks.

The only technology capable of detecting attacks from within the control network using protocols, messages and values ​​allowed within the same, but in order or frequency other than normal is the use of intrusion detection systems that support the deep protocol behavior inspection (DPBI) with the ability to implement correlation of operational events.

The implementation of these technologies in critical infrastructures control networks should be considered seriously by those responsible for the cyber security of these facilities and the authorities responsible for monitoring compliance with the PIC 8 / 2011 Act.


In the future, Sequence-aware NIDS (S-NIDS), or similar technologies, may help simplify the implementation of these systems in control networks significantly improving the behavior pattern generation and subsequent maintenance, protecting processes and cyber-physical systems on critical infrastructures.